Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 12 Actuators X53 / X54 25.09.2013
No. Parameter
606
Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
Index 1 = air
Greatest position error where an error is securely detected
error detection band: (parameter 606 -0.6°) up to parameter 606
610
Fuel 1: Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
Index 1 = air
Greatest position error where an error is securely detected
error detection band: (parameter 606 -0.6°) up to parameter 606
Error
code
Diagnostic
code
Meaning for the LMV36... system
86 0 Fuel actuator: Position error
87 0 Air actuator: Position error