Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 28 Parameter level 25.09.2013
)
Air
Figure 99: Setting the curvepoints
Note
Curvepoints P2 to P8 are automatically computed as a straight line between P1 and P9.
Example 1 = gas modulating
P0, P1 and P9 are set as described: Curvepoint Value 1
fuel
Value 2
air
P0
30.0 22.0
P1
32.0 24.0
P9
80.0 90.0
P2 through P8 have automatically been
calculated:
Curvepoint Value 1
fuel
Value 2
air
P2 38.0 32.3
P3
44.0 40.5
P4
50.0 48.8
P5
56.0 57
P6
62.0 65.3
P7
68.0 73.5
P8
74.0 81.8