5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions
266 6SE6400-5AW00-0BP0
Table 5-4 Data for braking resistors
I
DC_max
for Frame Size
Rated voltage V
DC_max
A B C D E F
230 V 410 - 420 V
2,33 A
(180 )
6,18 A
(68 )
10,77 A (39 )
15,56 A (27 )
41,0 A
(10 )
60,3 A
(6,8 )
124,2 A
(3,3 )
400 V 820 - 840 V
2,15 A
(390 )
5,25 A
(160 )
15 A
(56 )
30,4 A
(27 )
54,7 A
(15 )
100,0 A
(8,2 )
575 V 1020 V - -
8,5 A (120 )
12,4 A (82 )
26,2 A
(39 )
37,8 A
(27 )
85,0 A
(12 )
Table 5-5 MICROMASTER 440 Specifications
In order that the system is in compliance with UL, UL-certified fuses must be
used with the appropriate rated current.
Input voltage range 1 AC 200 V – 240 V, ± 10 %
(with built in Class A Filter)
Order No. 6SE6440- 2AB11
-2AA1
2AB12
-5AA1
2AB13
-7AA1
2AB15
-5AA1
2AB17
-5AA1
2AB21
-1BA1
2AB21
-5BA1
2AB22
-2BA1
2AB23
-0CA1
[kW] 0.12 0.25 0.37 0.55
0.75 1.1 1.5 2.2 3.0
Output Rating (CT)
[hp] 0.16 0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Output Power [kVA] 0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
CT Input Current 1) [A] 1.8 3.2 4.6 6.2 8.2 11.0 14.4 20.2 35.5
CT Output Current [A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6
Fuse [A] 10 10 10 16 16 20 20 32 40
Recommended 3NA 3803 3803 3803 3805 3805 3807 3807 3812 3817
for UL specified
* * * * * * * * *
[mm
2
] 1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0
Input Cable Min.
[awg] 18 18 18 16 16 14 14 12 10
[mm
2
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Input Cable Max.
[awg] 14 14 14 14 14 10 10 10 8
[mm
2
] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
Output Cable Min.
[awg] 18 18 18 18 18 18 18 18 16
[mm
2
] 2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Output Cable Max.
[awg] 14 14 14 14 14 10 10 10 8
[kg] 1.3 1.3 1.3 1.3 1.3 3.4 3.4 3.4 5.7
Weight
[lbs] 2.9 2.9 2.9 2.9 2.9 7.5 7.5 7.5 12.5
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America