5 MICROMASTER 440 specifications Issue 10/06
MICROMASTER 440 Operating Instructions
272 6SE6400-5AW00-0BP0
Input voltage range 3 AC 500 V – 600 V ± 10 % (Unfiltered)
Order No. 6SE6440
-
2UE17-
5CA1
2UE21-
5CA1
2UE22-
2CA1
2UE24-
0CA1
2UE25-
5CA1
2UE27-
5CA1
2UE31-
1CA1
2UE31-
5DA1
[kW] 0.75 1.5 2.2 4.0
5.5 7.5 11.0 15.0
Output Rating (CT)
[hp] 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0
Output Power [kVA] 1.3 2.6 3.7 5.8 8.6 10.5 16.2 21.0
CT Input Current 1) [A] 2.0 3.7 5.3 8.1 11.1 14.4 21.5 24.9
CT Output Current [A] 1.4 2.7 3.9 6.1 9.0 11.0 17.0 22.0
VT Input Current 1) [A] 3.2 4.4 6.9 9.4 12.6 18.1 24.9 30.0
VT-Output Current [A] 2.7 3.9 6.1 9.0 11.0 17.0 22.0 27.0
Fuse [A] 10 10 10 16 16 25 32 35
Recommended 3NA 3803-6 3803-6 3803-6 3805-6 3805-6 3810-6 3812-6 3814-6
for UL specified 3NE
*
*
*
*
*
*
*
1803-0
[mm
2
] 1.0 1.0 1.0 1.5 1.5 2.5 4.0 6.0
Input Cable Min.
[awg] 18 18 18 16 16 14 12 10
[mm
2
] 10.0 10.0 10.0 10.0 10.0 10.0 10.0 35.0
Input Cable Max.
[awg] 8 8 8 8 8 8 8 2
[mm
2
] 1.0 1.0 1.0 1.0 1.0 2.5 4.0 4.0
Output Cable Min.
[awg] 18 18 18 18 18 14 12 12
[mm
2
] 10.0 10.0 10.0 10.0 10.0 10.0 10.0 35.0
Output Cable Max.
[awg] 8 8 8 8 8 8 8 2
[kg] 5.5 5.5 5.5 5.5 5.5 5.5 5.5 16.0
Weight
[lbs] 12.1 12.1 12.1 12.1 12.1 12.1 12.1 35.0
Order No. 6SE6440- 2UE31-
8DA1
2UE32-
2DA1
2UE33-
0EA1
2UE33-
7EA1
2UE34-
5FA1
2UE35-
5FA1
2UE37-
5FA1
[kW] 18.5 22.0 30.0 37.0 45.0 55.0 75.0
Output Rating (CT)
[hp] 25.0 30.0 40.0 50.0 60.0 75.0 100.0
Output Power [kVA] 25.7 30.5 39.1 49.5 59.1 73.4 94.3
CT Input Current 1) [A] 30.0 35.0 48.0 58.0 69.0 83.0 113.0
CT Output Current [A] 27.0 32.0 41.0 52.0 62.0 77.0 99.0
VT Input Current 1) [A] 35.0 48.0 58.0 69.0 83.0 113.0 138.0
VT-Output Current [A] 32.0 41.0 52.0 62.0 77.0 99.0 125.0
Fuse [A] 50 63 80 80 125 160 160
Recommended 3NA 3820-6 3822-6 3824-6 3824-6 3132-6 3136-6 3136-6
for UL specified 3NE 1817-0 1818-0 1820-0 1820-0 1022-0 1224-0 1224-0
[mm
2
] 10.0 10.0 16.0 25.0 25.0 50.0 50.0
Input Cable Min.
[awg] 8 8 6 3 3 1/0 1/0
[mm
2
] 35.0 35.0 35.0 35.0 150.0 150.0 150.0
Input Cable Max.
[awg] 2 2 2 2 300 300 300
[mm
2
] 6.0 10.0 16.0 16.0 25.0 35.0 50.0
Output Cable Min.
[awg] 10 8 6 6 3 2 1/0
[mm
2
] 35.0 35.0 35.0 35.0 150.0 150.0 150.0
Output Cable Max.
[awg] 2 2 2 2 300 300 300
[kg] 16.0 16.0 20.0 20.0 56.0 56.0 56.0
Weight
[lbs] 35.0 35.0 44.0 44.0 123.0 123.0 123.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 500 V without line commutating reactor.