Connection to PROFINET IO
7.5 Structure of the data records
SCALANCE X-200
166 Configuration Manual, 03/2015, C79000-G8976-C285-06
7.5.2
Data record 5
Data record 5 supplies the current alarm setting for this port
Access: Read-only
typedef struct {
Word BlockType;
Word BlockLength;
Byte BlockVersionHigh;
Byte BlockVersionLow;
DWord status; };
BlockType:
1: Constant
BlockLength:
6: Constant in device data, designates the length without Type+ Length
BlockVersionHigh:
1: Constant in device data, designates the major version
BlockVersionLow:
1: Constant in device data, designates the minor version
Status:
Reserved
Bits 8...31
C-PLUG_status
Bits 4...7
Reserved
Bits 2...3
Fault_line_status
Bit 1
Power line redundancy
Bit 0
0 Information regarding
the configuration plug
of the network compo-
nent
0: C-PLUG inserted
and ok
1:C-PLUG not inserted
2: C-PLUG inserted but
not ok (incorrect type)
3: C-PLUG inserted but
not ok (checksum error)
Information about the
current error status
0: Fault line passive
1: Fault line active
This bit provides infor-
mation about the redun-
dant power supply
0: not redundant
1: redundant