Menus in the WBM
5.2 The X-200 menu
SCALANCE X-200
Configuration Manual, 03/2015, C79000-G8976-C285-06
71
Syntax of the Command Line Interface
Table 5- 11 Fault Mask - CLI\X200>
Displays information on the "X-200" menu item.
fault Displays the fault status.
power [<E|D> [lines]] Specifies a fault mask for the power supplies Power
Administrator only
others <R|S|F> <E|D> Specifies the fault mask for:
R - Ring Redundancy Manager
S - Standby Manager (only relevant for IRT devices)
F - FMP Event (only relevant for FM devices)
Administrator only
downmask <1-n> <E|D> Specifies a port mask for the ports for which the
monitoring of a link down event is enabled.
Administrator only
upmask <1-n> <E|D> Specifies a port mask for the ports for which the
monitoring of a link up event is enabled.
Administrator only
On this page, you can set the ports for media redundancy and the required redundancy
mode.
-200 IE switches as of firmware V4.0 support the media redundancy methods MRP and
-200 IE switches with firmware V3.1 and older, X-300 and X-400 IE switches with firmware
V2.3 and older and OSMs/ESMs support only the HRP method.
t to configure an MRP ring, the devices can be interconnected to form a ring
without any extra configuration. In this case, the default ring ports must be used, see
Appendix
Default ring ports (Page 177). The default role "Automatic Redundancy Detection"
automatically configures the ring.
If an HRP ring is configure
d, exactly one device in the ring must be set to the HRP Manager
role. All other devices in the ring must be set to either "Automatic Redundancy Detection" or
"HRP Client".
If an HRP ring is configured in which a linear bus is set up in which a device is s
et to HRP
manager and the other devices have the setting "Automatic Redundancy Detection", the
error message "other RM in ring" is output. This disappears after connecting the linear bus to
form a ring.