9 Operation at Use of a PC
9.3 Configuration of the Device
245SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.7.5.3 Mapping – Indications
At Indications, the indications are defined which are read by a selected Modbus slave device.
Default Settings and Settings of the Modbus Slave Device 1
Table 9-35 Settings for assignment of the indications of the Modbus slave device 1
Parameter Default Setting Setting Range
Name Indication x Slv 1
(x = 1 to 6)
Max. 31 characters
Register type -none- -none-
Coil status registers
Input status registers
Input registers
Holding registers
For -none-, the assignment is ignored
and the corresponding indication cannot
be selected for other functions.
Data format on bus
(see also Table 9-36.)
1 Bit 1 Bit
1 Bit in UInt32
Register number 1 1 to 65 535
Bit offset
(only relevant for register types
Input register or Holding register)
0 0 to 15 (for Data format 1 Bit)
0 to 31 (for Data format 1 Bit in UInt32)
Table 9-36 Data format on Bus
Data Format
on Bus
Description Setting
Range
Invalid
recognition
Used by (example)
1 Bit 1 bit (for all register types; addi-
tionall select Bit offset for Input
register and Holding register)
0 = of
1 = on
none SICAM P50 7KG775,
SENTRON 3WL/3VL,
SIPROTEC4
1 Bit in UInt32 1 bit in 2 successive Input regis-
ters or Holding registers which
have to be read together.
0 = of
1 = on
none SENTRON PAC3x00