Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-57
Edition 12.2003
Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1
Status 1
(D01
low byte)
S: Slave
was para-
meterized
from
another
master
S: Last
parameter
telegram
was
erroneous
M:
Erroneous
slave
response
S:
Reques-
ted func-
tion is not
supported
S:
Diagnos-
tics entry
in the
specific
diagnos-
tics area
S: Config.
data dont
match
S: Slave
still not
ready for
data
transfer
M: Slave
cannot be
addressed
on the bus
Status 2
(D01
high byte)
M: Slave
entered
as ”not
active”
(not used)
S:
Slave has
received a
Sync
command
S:
Slave has
received
the
Freeze
command
S:
Response
moni-
toring
activated
S: 1
(fixed)
S:
Diagnos-
tic data
must be
retrieved
S:
Parameteri
zation and
configuring
required
Status 3
(D02
low byte)
S/M: Not
all dia-
gnostics
data can
be trans-
ferred
- - - - - - -
Table 3-26 Significance of the individual bits, status 1, 2 and 3
− M: Master identifies diagnostics data
− S: Slave identifies diagnostics data
Master PROFIBUS address
• PROFIBUS address of the master which had parameterized this
slave.
If this slave is not parameterized, then FFh is used.
Identification number
• High/low byte:
This identifies the slave type.
All additional diagnostic data are slave-specific.
Generally (standard DP slave) the diagnostic blocks follow: Device-
related, identification-related and channel-related diagnostics. Not all
slave-specific diagnostic blocks must be available.
Each block is preceded by a header byte. The diagnostics block is
identified by bit 7 and bit 8:
Bits, status 1, 2
and 3