Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-107
Edition 12.2003
when it comes to a utility, then the other partner can respond to the
flag or indication (".ind") of this utility.
• "Max. No. of parallel tasks" is used to define how many tasks can be
simultaneously executed via this communications association. The
"Transmit" data of a partner must be lower or the same as the
"Receive" data of the other partner. The "Transmit" and "Receive"
data refer to the tasks, not the net data! The "Transmit" data should
correspond to the number of communication function blocks from the
CFC configuring, which use this communications association as client.
Features:
• Non-cyclic data transfer
• SIMADYN D is exclusively a server.
• (At least one) connection must be configured for each remote client.
• Remote client establishes the connection and initiates data transfer
• The remote client can access each object in the SIMADYN D object
directory.
• Several utilities are possible in parallel
Application:
• All SIMADYN D utilities, where SIMADYN D is a server.
Communications reference :
Type
:
Non-cyclic server
Association type : MMAZ Local LSAP :
External address : Remote LSAP :
Max. PDU length : 241 Monitoring interval : 0 s
Supported utility :
Read : .ind Write : .ind
Get OV (detailed version) : .ind Information report : no
Symbolic addressing : .ind
Max. No. of parallel tasks:
Transmitting : 0 Receiving : 1
Designator :
Table 3-47 Mask, "Non-cyclic server"
Non-cyclic server

Table of Contents

Other manuals for Siemens SIMADYN D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMADYN D and is the answer not in the manual?

Siemens SIMADYN D Specifications

General IconGeneral
BrandSiemens
ModelSIMADYN D
CategoryControl Systems
LanguageEnglish

Related product manuals