EasyManua.ls Logo

Siemens SIMADYN D - Page 308

Siemens SIMADYN D
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-219
Edition 12.2003
NOTE
The maximum number of interconnections of different inputs which
are changed with BICO technology, which are saved in the change
memory, are, for
technology module T400: approx. 1600
Application module FM 458: approx. 400
CPU module in the SIMADYN D subrack: approx. 400
Using BICO- technology, you can only change existing
interconnections between block I/O, but you cannot delete them.
Using BICO technology, you cannot establish a new
interconnection at inputs which are not connected.
Changes made to the interconnections of block I/O using BICO
technology, are only effective when updating the project in the CFC,
if they were saved.
For changes made to the interconnections of block I/O using BICO
technology, when type checking the connections, the same rules
apply as for CFC.
!
CAUTION
The pseudo comment @DATX is not supported by the CFC test mode.
When changing an interconnection, where @DATX is available as
pseudo comment at the block input, the value for this connection is
updated again, but still maintaining the data consistency mechanisms.
Thus, the pseudo comment @DATX is no longer valid.
Remedy: Re-compile and re-load the user program.

Table of Contents

Other manuals for Siemens SIMADYN D

Related product manuals