Technical specifications
14.1 Standards, approvals and safety notes
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
273
Use in industrial environments
SIMATIC products are designed for use in industry.
Table 14- 1 Use in industrial environments
Area of applica-
tion
Interference emission requirements
Interference immunity requirements
Industry
EN 61000-6-4:2007 + A1:2011
EN 61000-6-2:2005
Use in residential areas
Note
The ET
200SP is intended for use in industrial areas; use in residential areas may have an
impact on radio/TV reception.
If you want to use the ET 200SP distributed I/O system in residential areas, you must ensure
that its radio frequency interference emission complies with limit class B in accordance with
EN 55011.
Suitable measures for achieving RF interference level Class B include, for example:
Installation of the ET 200SP distributed I/O system in grounded control cabinets/control
boxes
Use of filters in the supply lines
Reference
The certificates for the markings and approvals can be found on the Internet under
Service&Support (http://www.siemens.com/automation/service&support).