Configuration control (option handling)
9.1 Configuring
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
175
9.1
Configuring
Requirements
Configuration control is supported by the ET 200SP distributed I/O system with both an
ET 200SP CPU and with interface modules via PROFINET IO and PROFIBUS DP.
Centrally for ET 200SP CPU:
STEP 7 Professional V13 Update 3 or higher
CPU 1510SP-1 PN/CPU 1512SP-1 PN
Firmware version V1.6 or higher
All modules of the CPU must be able to start up even with different configurations.
The startup parameter "Comparison preset to actual configuration" of the CPU is set to
"Startup CPU even if mismatch" (default setting) and the module parameter
"Comparison preset to actual module" of the module is set to "From CPU" (default
setting).
or
The module parameter "Comparison preset to actual module" for the module is set to
"Startup CPU even if mismatch".
Distributed via PROFINET IO:
Engineering Tool (e.g. STEP 7)
IM 155-6 PN BA/ST/HF/HS
You have assigned the interface module to an IO controller.
Distributed via PROFIBUS DP:
Engineering Tool (e.g. STEP 7)
IM 155-6 DP HF
You have assigned the interface module to a DP master.
The startup parameter is set to "Operate if preset configuration does not match actual
configuration"