EasyManua.ls Logo

Siemens Simantic ET200SP - Connecting the supply voltage to the CPU;interface module

Siemens Simantic ET200SP
311 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
5.11 Connecting the supply voltage to the CPU/interface module
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
99
5.11
Connecting the supply voltage to the CPU/interface module
Introduction
The supply voltage of the CPU/interface module is supplied by means of a 4-pin connector
plug located on the front of the CPU/interface module.
Power supply unit
Only use power supply units of type SELV/PELV with safe electrically isolated functional
extra low voltage (≤ 28.8 V DC).
Connection for supply voltage (X80)
The connections have the following meaning:
Ground of the supply voltage
Ground of the supply voltage for looping through (permitted value 10 A)
+ 24 V DC of the supply voltage for looping through (permitted value 10 A)
Spring release
+ 24 V DC of the supply voltage
1L+ and 2L+ and 1M and 2M are internally jumpered.
Figure 5-11 Supply voltage connection
The maximum cross-section of the connection is 2.5 mm
2
. A strain relief is not present. The
connector plugs provide you with the option of looping the supply voltage through without
interruption, even when it is unplugged.
Requirements
Only wire up the connector plug when the supply voltage is turned off.
Follow the wiring rules (Page 87).
Required tools
3 to 3.5 mm screwdriver

Table of Contents