Configuration control (option handling)
9.2 Creating the control data record
Distributed I/O system
180 System Manual, 12/2016, A5E03576849-AG
Byte
Element
Code
Explanation
9
Additional function for slot 3
: : :
4 + ((max. slot -
1) × 2)
Server module slot Server module slot as-
signment in the station
option*
4 + ((max. slot -
1)× 2) + 1
Additional function for server module slot
* The server module must be present in the station option and must not be marked as empty slot (BU cover).
9.2.3
Control data record for an interface module
Slot assignment
The following table shows the possible slots for the various modules for an
ET 200SP interface module:
Table 9- 3 Slot assignment
Modules
Possible slots
Comment
Interface module 0 The interface module (slot 0) is not an element of the configu-
ration control, but instead controls this.
Station extension
BA-Send
1 For mixed configuration with ET 200AL modules, BA-Send is
always on slot 1.
ET 200SP I/O module
1 - 12
for IM 155-6 PN BA
Downstream from the interface module
1 - 30
for IM 155-6 PN HS
1 - 32 for IM 155-6 PN ST,
IM 155-6 DP HF
1 - 64
for IM 155-5 PN HF
Server module
1 - 13
for IM 155-6 PN BA
The server module completes the configuration of the
ET 200SP station after the last I/O module.
1 - 31
for IM 155-6 PN HS
1 - 33 for IM 155-6 PN ST,
IM 155-6 DP HF
1 - 65 for IM 155-5 PN HF
ET 200AL I/O module
34 - 49
for IM 155-6 DP HF
For mixed configuration with ET 200AL modules
66 - 81
for IM 155-6 PN ST,
IM 155-6 PN HF