Technical specifications
14.6 Insulation, protection class, degree of protection and rated voltage
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
281
Climatic environmental conditions
The table below shows the permissible climatic environmental conditions for the ET 200SP
distributed I/O system:
Table 14- 11 Climatic environmental conditions
Environmental conditions
Permissible range
Comments
Temperature:
horiz. mounting position:
vertical mounting position:
0 to 60 °C
0 to 50 °C
-
Permitted temperature
change
10 K/h -
Relative humidity from 10 to 95% Without condensation, corresponds to rela-
tive humidity (RH) stress grade 2 in accord-
ance with IEC 61131 part 2
Barometric pressure 1080 hPa to 795 hPa Corresponds to an altitude of -1000 to
2000 m
Pollutant concentration SO
2
: <0.5 ppm;
RH <60%, no condensation
H
2
S: <0.1 ppm;
RH <60%, no condensation
-
ISA-S71.04 severity level G1; G2; G3
-
14.6
Insulation, protection class, degree of protection and rated voltage
Insulation
The insulation for the I/O modules is designed in accordance with the requirements of
EN 61131-2:2007. The insulation for the motor starters is designed in accordance with the
requirements of IEC 60947-1.
Note
In the case of modules with 24 V DC (SELV/PELV) supply voltage, galvanic isolations are
tested with 70
7 V DC (type test).
Pollution degree/overvoltage category according to IEC 61131
Pollution degree 2
Overvoltage category: II
Pollution degree/overvoltage category according to IEC 60947
Pollution degree 2
Overvoltage category: III