Wiring
5.12 Connecting interfaces for communication
Distributed I/O system
118 System Manual, 12/2016, A5E03576849-AG
5.12.7
Connecting PROFINET IO to the interface module via the BA LC/RJ45
BusAdapter
Introduction
You connect PROFINET IO to the interface module via the BA LC/RJ45 BusAdapter:
Optically coupled to glass fiber-optic cables with an LC connector (port 1) or
Electrically with a standard RJ45 connector (port 2)
To do this, screw the BA LC/RJ45 BusAdapter onto the interface module and insert the LC
connector or RJ45 plug.
You can loop through the PROFINET IO via the integrated 2-port switch. You can use any
port of the BusAdapter for feeding or for looping through. The integrated media converter
converts the signals automatically.
Glass fiber-optic cable LC
RJ45
Figure 5-26 BA LC/RJ45 BusAdapter
Attaching LC connectors
You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting PROFINET IO to an interface module via BA 2×LC
BusAdapter (Page 115).
Connecting RJ45 plugs
You can find more information about the required tools, accessories and procedures in the
section Connecting PROFINET IO to an interface module via BA 2×RJ45 BusAdapter
(Page 101).