Wiring
5.8 Connecting cable shields for I/O modules
Distributed I/O system
92 System Manual, 12/2016, A5E03576849-AG
5.8
Connecting cable shields for I/O modules
Introduction
You need the shield connector to contact cable shields (e.g. for analog modules). The
shield connector conducts interference currents on cable shields to ground via the
mounting rail. It is not necessary to contact the shield at where the cable enters the
cabinet.
Attach the shield connector to the BaseUnit.
The shield connector consists of a shield contact and a shield terminal.
The shield connector is automatically connected to the functional ground (FG) of the
mounting rail after installation.
Requirements
BaseUnit with a width of 15 mm
The shield terminal is suitable for cables with max. 7 mm each.
Figure 5-6 Shield terminal
Required tools
Stripping tool