Wiring
5.8 Connecting cable shields for I/O modules
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
93
Procedure
Watch the "Wiring BaseUnits" video sequence
(http://support.automation.siemens.com/WW/view/en/95886218)
To connect the cable shield, follow these steps:
1. If necessary, connect the supply voltage L+ and ground to the BaseUnit.
2. Press the shield contact up into the mount until you hear it click into place.
3. Remove the cable insulation material around the shield terminal.
Connect the cable to the BaseUnit and place the cable in the shield contact.
4. Insert the shield terminal into the shield contact.
5. Tighten the shield terminal with approximately 0.5 Nm.
Mount
Insulation material removed (approx. 20
mm)
Supply voltage L+, ground
Cable to the encoder
Shield contact
Shield terminal
Flat connector for push-on contacts
(6.3 × 0.8 mm)
Figure 5-7 Mounting the shield contact