Commissioning
10.3 Commissioning the ET 200SP on PROFIBUS DP
Distributed I/O system
208 System Manual, 12/2016, A5E03576849-AG
ET 200SP as a DP slave
Configuration example
To use the ET 200SP distributed I/O system as a DP slave, you need the IM 155-6 DP HF.
Figure 10-6 ET 200SP as a DP slave
To commission the ET 200SP distributed I/O system as a DP slave on PROFIBUS DP, we
recommend the following procedure:
Table 10- 6 Procedure for commissioning the ET 200SP as a DP master for PROFIBUS DP
Installing ET 200SP (with IM 155-6 DP HF)
Section Installation (Page 54)
2 Setting the PROFIBUS address on the interface
module
Section Interface module
(http://support.automation.siemens
.com/WW/view/en/55683316/1333
3 Connecting ET 200SP
• Supply voltages
• PROFIBUS DP
• Sensors and actuators
Section Wiring (Page 75)
4 Configuring DP master (including PROFIBUS
Documentation of the DP master
Switching on supply voltages for DP master
Documentation of the DP master
6 Switching on supply voltages for DP slaves Interface module
(http://support.automation.siemens
.com/WW/view/en/55683316/1333
Download configuration to the DP master