Commissioning
10.3 Commissioning the ET 200SP on PROFIBUS DP
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
207
For commissioning of the ET 200SP distributed I/O system as an I-slave on the
PROFIBUS DP, we recommend the following procedure:
Table 10- 5 Procedure for commissioning the ET 200SP as an I-slave for PROFIBUS DP
Installing ET 200SP (with CPU and CM DP)
Section Installation (Page 54)
2 Connecting ET 200SP
• Supply voltages
• PROFIBUS DP
• Sensors and actuators
Section Wiring (Page 75)
3 Configuring DP master (including PROFIBUS
Documentation of the DP master
4 Inserting a SIMATIC memory card in the I-slave
(CPU)
Section Removing/inserting a
SIMATIC memory card on the CPU
5 Configuring I-slave (including PROFIBUS ad-
dress)
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
Switching on supply voltages for DP master
Documentation of the DP master
7 Switching on supply voltages for I-slaves CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
8 Loading configuration in the DP master and I-
STEP 7 online help
9 Switching DP master and I-slaves to RUN Documentation of the DP master
and CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
10 Checking LEDs CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
11 Testing inputs and outputs The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. See
the Test functions and fault resolu-
tion
(http://support.automation.siemens
.com/WW/view/en/90466439/1333