Interrupts/diagnostic alarms
14.4 Diagnostics response
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
126 Manual, 07/2018, A5E42674880-AA
Parameter assignment
The following table shows the necessary parameters:
Table 14- 16 Parameter assignment
Parameter
Nominal value current
0 ... 99999 A
Current transformer primary current 1 ... 99999 A
Current transformer secondary current
1 ... 16000 A
Low limit for current measurement
0 ... 20% *
* 0% means deactivation of the function
Example
The following figure is a schematic diagram of the principle of operation:
Nominal current
Low limit measured current
Measured value
Returned value
Figure 14-8 Behavior in the event of value falling below "Low limit for measuring current undershot"