Energy counters
7.4 Example of measuring and resetting an energy meter
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
66 Manual, 07/2018, A5E42674880-AA
7.4
Example of measuring and resetting an energy meter
The following figure shows resetting and starting/stopping with activated gating using the
energy meter as an example:
The counter is reset to the value specified in the configuration. The gate is closed. The counter does not count.
The gate is opened via the control byte 1 in the output data of the user data variant. The counter counts.
The configured current low limit has been violated. The counter does not count.
The gate is closed. The counter does not count. A new start value is written to the measured value data record 143
(Page 232) with the WRREC instruction.
The gate is opened again via the control byte 1 in the output data of the user data variant. The counter counts with
the new start value.
The counter is reset via the control byte 1 in the output data of the user data variant. The counter counts from the
new start value that was transferred via the measured value data record 143.
Figure 7-10 Example of an energy meter