Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
84 Manual, 07/2018, A5E42674880-AA
Minimum and maximum values
10
10.1
Minimum and maximum values
Introduction
The AI Energy Meter HF determines the respective highest and lowest measured or
calculated value for a series of measured and calculated values. The values are stored
retentively in the module and can be read using measured value data records DS 144
(Page 237), DS 145 (Page 243), DS 154 (Page 239) and DS 155 (Page 245).
Benefits
Using the stored minimum and maximum values, for example, you can detect further
irregularities in addition to limit monitoring.
Calculation of minimum and maximum values
Minimum and maximum values are only calculated for the phases in accordance with the
configured connection type. Existing minimum and maximum values that have not been
calculated are assigned initial values. If faults such as under or overcurrent occur during
operation, new minimum and maximum values are calculated.
The measured and calculated values are initialized as follows during commissioning of the AI
Energy Meter HF so that the first calculation of minimum and maximum values supplies a
plausible result:
Maximum values for measured and calculated values: Minimum values
Minimum values for measured and calculated values: Maximum values
Minimum and maximum values are determined as "slave pointer procedures" from the start
of calculation. Start is effective as of activation of the function or after a reset. The module
uses the current actual value as the start value.
When you activate the parameter "Enable minimum and maximum value calculation gate",
the calculation only starts if the corresponding DQ bit ("gate open") was set (output data Byte
1, Bit 2 = "1"). You can stop the calculation at any time by deactivating the parameter or
closing the gate. Calculation starts again after reactivation. The gate for calculation of the
minimum and maximum values functions in the same way as the gate for energy meters.
Configuring
You configure the following settings in STEP 7:
Enable calculation of minimum and maximum values
Enable minimum and maximum value calculation gate

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals