Interrupts/diagnostic alarms
14.4 Diagnostics response
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
114 Manual, 07/2018, A5E42674880-AA
14.4.1
Voltage diagnostics
14.4.1.1
Diagnostics: Overflow/underflow
Introduction
You use the parameter "Tolerance factor overvoltage/undervoltage" to define a tolerance
range around the set nominal value voltage at the operating point. If the effective value of the
primary voltage exceeds this tolerance range, the module reports the diagnostics "overflow"
or "underflow".
Calculation of tolerance value measuring voltage
The tolerance value measuring voltage is calculated with the following formula:
Tolerance value measuring voltage = "Nominal value voltage" ± ("Tolerance factor
overvoltage/undervoltage [%]" × "Nominal value voltage")
The "Nominal value voltage" is the primary voltage at the operating point.
Parameter assignment
The following table shows the necessary parameters:
Table 14- 6 Parameter assignment
Parameter
Power quality analysis functions
Enable
Diagnostics overflow
Enable
Diagnostics underflow
Enable
Nominal value voltage 1 ... 999999 V
Voltage transformer primary voltage
1 ... 999999 V
Voltage transformer secondary voltage
1 ... 500 V
Tolerance factor overflow/underflow
10 ... 50%