Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
94 Manual, 07/2018, A5E42674880-AA
Phase-based measured values
The AI Energy Meter HF makes the measured values of individual phases available.
● Through the user data variants
– Phase-specific measurement Phase L1 with user data variants 154 (9A
H
) and
155 (9B
H
)
– Phase-specific measurement Phase L2 with user data variants 156 (9C
H
) and
157 (9D
H
)
– Phase-specific measurement Phase L3 with user data variants 158 (9E
H
) and
159 (9F
H
)
● Via measured value data records
– Phase-specific measurement for the phases L1, L2 and L3 with data record 142
– Phase-specific measurement for phase L1 with data record 147
– Phase-specific measurement for phase L2 with data record 148
– Phase-specific measurement for phase L3 with data record 149
Through the user data variants 154 (9A
H
) to 159 (9F
H
) you can evaluate the following
measured values for each phase of an AC / three-phase network:
● Quality information
● Current and voltage
● Active, reactive and apparent power
● Active, reactive and apparent energy
● Power factor
You can find the structure of the user data variants in appendix User data variants
(Page 205).