Power quality analysis functions
11.3 Reactive power compensation
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
91
11.3
Reactive power compensation
Use the power factor of the fundamental for the reactive power compensation.
When you activate the power quality analysis function, the power factor of the fundamental is
available in the measured value data record DS 160 (Page 259) or in the user data.
See also
User data variants (Page 205)
11.4
Detection of residual current
For the residual current analysis (function "Tamper Detect" = Detection of unauthorized
interventions), the total current must be determined:
Isum L1L2L3 (t) = IL1 (t) + IL2 (t) + IL3 (t)
The instantaneous residual current If is obtained by subtracting the results of the current
neutral current In from the total current:
If = Isum L1L2L3 In
Analysis starts immediately after parameter assignment. The measured value "Total current
IL1+IL2+IL3-IN" (ID = 61153) returns the residual current. It is contained in DS 160, for
example. You can monitor a threshold relevant for your application for a limit value (see
function Limit monitoring (Page 77)).
Requirements
"3P4W" or "3P4WI" is parameterized as the connection type.
The same current transformers are connected to all three phases.
The parameter "Reverse current direction" is parameterized identically for all three
phases.
The neutral current is parameterized with "Measuring".
The residual current analysis is activated in the parameter assignment.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals