Page #252 background imageLoading...
Page #252 background image
Measured value data records
E.9 Measured value data record for phase-based measured values L2 (DS 148)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
251
E.9
Measured value data record for phase-based measured values L2
(DS 148)
E.9.1
Measured value data record for phase-based measured values L2 (DS 148)
version 0
Measured variables of the module
The measured value identification (measured value ID) is an index which references the
overview table of the measured variables in appendix B (Measured variables (Page 163)).
Byte
Measured variable
Data
type
Unit
Value range
Meas-
ured
value
ID
0
Version
BYTE
-
0
-
1
Reserved
BYTE
-
0
-
2...3 Qualifier L2 WORD Bit field 0b 00 00 00 00
0b qq 00 00 xx
65501
4...7
Voltage UL1-N
REAL
V
0.0 ... 1000000.0
2
8...11
Current L2
REAL
A
0.0 … 100000.0
8
12...15
Apparent power L2
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
11
16...19
Active power L2
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
14
20...23
Reactive power Qtot L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
23
24...27
Power factor L2
REAL
-
0.0 ... 1.0
20
28...31
Phase angle L2
REAL
°
0.0 ... 360.0
61198
32...39
Apparent energy L2
LREAL
VAh
0.0 ... 1.8 x 10
308
61204
40...47
Total active energy L2
LREAL
Wh
-1.8 x 10
308
to +1.8 x 10
308
61205
48...55
Total reactive energy L2
LREAL
varh
-1.8 x 10
308
to +1.8 x 10
308
61206
56...59
Max. voltage UL1-N
REAL
V
0.0 ... 1000000.0
41
60...63
Max. current L2
REAL
A
0.0 ... 100000.0
47
64...67
Max. apparent power L2
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
50
68...71
Max. active power L2
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
53
72...75
Max. reactive power Qtot L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62260
76...79
Max. power factor L2
REAL
-
0.0 ... 1.0
59
80...83
Min. voltage UL1-N
REAL
V
0.0 ... 1000000.0
71
84...87 Min. current L2 REAL A 0.0 ... 100000.0 77
88...91
Min. apparent power L2
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
80
92...95
Min. active power L2
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
83
96...99
Min. reactive power Qtot L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62280
100...103
Min. power factor L2
REAL
-
0.0 ... 1.0
89

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C