Measured value data records
E.8 Measured value data record for phase-based measured values L1 (DS 147)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
250 Manual, 07/2018, A5E42674880-AA
Byte
Measured variable
Data
type
Unit
Value range
Meas-
ured
value
ID
128...131
Fundamental current L1
REAL
A
0.0 ... 100000.0
62123
132...135 Fundamental apparent power L1 REAL VA -3.0 x 10
9
… +3.0 x 10
9
62125
136...139
Fundamental reactive power L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62124
140...143 Fundamental active power L1 REAL W -3.0 x 10
9
… +3.0 x 10
9
62126
144...147
Fundamental cos φ active factor L1
REAL
-
-1.0 ... 1.0
62127
148...151
Max. fundamental voltage L1
REAL
V
0.0 ... 760.0
62152
152...155
Max. fundamental current L1
REAL
A
0.0 ... 100000.0
62153
156...159
Max. fundamental apparent power L1
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
62155
160...163
Max. fundamental reactive power L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62154
164...167
Max. fundamental active power L1
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
62156
168...171
Max. fundamental cos φ active factor L1
REAL
-
-1.0 ... 1.0
62157
172...175
Min. fundamental voltage L1
REAL
V
0.0 ... 440.0
62172
176...179
Min. fundamental current L1
REAL
A
0.0 ... 100000.0
62173
180...183
Min. fundamental apparent power L1
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
62175
184...187
Min. fundamental reactive power L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62174
188...191
Min. fundamental active power L1
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
62176
192...195
Min. fundamental cos φ active factor L1
REAL
-
-1.0 ... 1.0
62177
196...199
THD+N voltage L1
REAL
1%
0% to 100%
62120
200...203
THD+N current L1
REAL
1%
0% to 100%
62121
204...207
Max. THD+N voltage L1
REAL
1%
0% to 100%
62150
208...211 Max. THD+N current L1 REAL 1% 0% to 100% 62151
212...215
Min. THD+N voltage L1
REAL
1%
0% to 100%
62170
216...219
Min. THD+N current L1
REAL
1%
0% to 100%
62171
220...223
Voltage dip - value L1
REAL
V
0.0 ... 440.0
62194
224...227
Voltage dip - duration L1
REAL
ms
0.0 ... 100000.0
62199
228...231
Voltage swell - value L1
REAL
V
0.0 ... 440.0
62195
232...235 Voltage swell - duration L1 REAL ms 0.0 ... 100000.0 62200
236...239
Voltage peak value L1
REAL
V
0.0 ... 440.0
62196
240...243
Current peak value L1
REAL
A
0.0 ... 100000.0
62197
244...247
Overcurrent value L1
REAL
A
0.0 ... 100000.0
62198

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C