EasyManuals Logo

Siemens SIMATIC ET 200SP User Manual

Siemens SIMATIC ET 200SP
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
Interrupts/diagnostic alarms
14.4 Diagnostics response
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
123
The following table shows the parameter assignment for the example:
Table 14- 13 Parameter assignment
Parameter
Power quality analysis functions
Enable
Determination of voltage peak value L1 Enable
Determination of voltage peak value L2
Enable
Determination of voltage peak value L3
Enable
The module detects the voltage peak in phase 1 and sets the qualifier bit 2 for phase 1. You
can find the maximum voltage value, for example, in the data record DS 160 in bytes 174 to
177 ("Voltage peak value L1").
14.4.2
Current diagnostics
14.4.2.1
Diagnostics: Overload
Introduction
As long as one of the following conditions is met, the module reports the diagnostics
"Overload" for each phase:
If the tolerance value measured current parameterized for each phase is exceeded for the
tolerance time overcurrent parameterized for each phase.
If the maximum measured current of the AI Energy Meters HF is exceeded:
Secondary measured current: 12 A
Calculation of tolerance value measured current
The tolerance value measured current is calculated with the following formula:
Tolerance value measured current = "Nominal value current" + ("Tolerance factor
overcurrent [%]" × "Nominal value current")
The "Nominal value current" is the primary current at the operating point.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals