Measured value data records
E.9 Measured value data record for phase-based measured values L2 (DS 148)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
252 Manual, 07/2018, A5E42674880-AA
E.9.2
Measured value data record for phase-based measured values L2 (DS 148)
version 1
Measured variables of the module
The measured value identification (measured value ID) is an index which references the
overview table of the measured variables in appendix B (Measured variables (Page 163)).
Byte
Measured variable
Data
type
Unit
Value range
Meas-
ured
value
ID
0
Version
UINT8
-
1
-
1
Reserved
UINT8
-
0
-
2...3 Qualifier L2 WORD Bit field 0b 00 00 00 00
0b qq 00 00 xx
65501
4...7
Voltage L2-N
REAL
V
0.0 ... 1000000.0
2
8...11
Current L2
REAL
A
0.0 … 100000.0
8
12...15
Apparent power L2
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
11
16...19
Active power L2
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
14
20...23
Reactive power L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
23
24...27
Power factor L2
REAL
-
0.0 ... 1.0
20
28...31
Phase angle L2
REAL
°
0.0 ... 360.0
61198
32...39
Apparent energy L2
LREAL
VAh
0.0 ... 1.8 x 10
308
61204
40...47
Total active energy L2
LREAL
Wh
-1.8 x 10
308
... +1.8 x 10
308
61205
48...55
Total reactive energy L2
LREAL
varh
-1.8 x 10
308
... +1.8 x 10
308
61206
56...59
Max. voltage UL2-N
REAL
V
0.0 ... 1000000.0
41
60...63
Max. current L2
REAL
A
0.0 ... 100000.0
47
64...67
Max. apparent power L2
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
50
68...71
Max. active power L2
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
53
72...75
Max. reactive power L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62260
76...79
Max. power factor L2
REAL
-
0.0 ... 1.0
59
80...83
Min. voltage UL2-N
REAL
V
0.0 ... 1000000.0
71
84...87 Min. current L2 REAL A 0.0 ... 100000.0 77
88...91
Min. apparent power L2
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
80
92...95
Min. active power L2
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
83
96...99
Min. reactive power Qtot L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62280
100...103
Min. power factor L2
REAL
-
0.0 ... 1.0
89
104...107
Reactive power Qn L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
17
108...111
Current L2 10-12 cycles
REAL
V
0.0 ... 760.0
62230
112...115
Current L2 10-12 cycles
REAL
A
0.0 ... 100000.0
62233
116...119
Max. reactive power Qn L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
56
120...123
Min. reactive power Qn L2
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
86
124...127
Fundamental voltage L2
REAL
V
0.0 ... 440.0
62222