EasyManua.ls Logo

Siemens SIMATIC ET 200SP - Measured Value Data Record for Phase-Based Measured Values L1 (DS 147) Version 1

Siemens SIMATIC ET 200SP
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Measured value data records
E.8 Measured value data record for phase-based measured values L1 (DS 147)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
249
E.8.2
Measured value data record for phase-based measured values L1 (DS 147)
version 1
Measured variables of the module
The measured value identification (measured value ID) is an index which references the
overview table of the measured variables in appendix B (Measured variables (Page 163)).
Byte
Measured variable
Data
type
Unit
Value range
Meas-
ured
value
ID
0
Version
UINT8
-
1
-
1
Reserved
UINT8
-
0
-
2...3 Qualifier L1 WORD Bit field 0b 00 00 00 00
0b qq 00 00 xx
65500
4...7
Voltage L1-N
REAL
V
0.0 ... 1000000.0
1
8...11
Current L1
REAL
A
0.0 … 100000.0
7
12...15
Apparent power L1
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
10
16...19
Active power L1
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
13
20...23
Reactive power L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
22
24...27
Power factor L1
REAL
-
0.0 ... 1.0
19
28...31
Phase angle L1
REAL
°
0.0 ... 360.0
61178
32...39
Apparent energy L1
LREAL
VAh
0.0 ... 1.8 x 10
308
61184
40...47
Total active energy L1
LREAL
Wh
-1.8 x 10
308
... +1.8 x 10
308
61185
48...55
Total reactive energy L1
LREAL
varh
-1.8 x 10
308
... +1.8 x 10
308
61186
56...59
Max. voltage L1-N
REAL
V
0.0 ... 1000000.0
40
60...63
Max. current L1
REAL
A
0.0 ... 100000.0
46
64...67
Max. apparent power L1
REAL
VA
-3.0 x 10
9
… +3.0 x 10
9
49
68...71
Max. active power L1
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
52
72...75
Max. reactive power L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62160
76...79
Max. power factor L1
REAL
-
0.0 ... 1.0
58
80...83
Min. voltage L1-N
REAL
V
0.0 ... 1000000.0
70
84...87 Min. current L1 REAL A 0.0 ... 100000.0 76
88...91
Min. apparent power L1
REAL
VA
-3.0 x 10
9
+3.0 x 10
9
79
92...95
Min. active power L1
REAL
W
-3.0 x 10
9
… +3.0 x 10
9
82
96...99
Min. reactive power Qtot L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
62180
100...103
Min. power factor L1
REAL
-
0.0 ... 1.0
88
104...107
Reactive power Qn L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
16
108...111
Current L1 10-12 cycles
REAL
V
0.0 ... 760.0
62130
112...115
Current L1 10-12 cycles
REAL
A
0.0 ... 100000.0
62133
116...119
Max. reactive power Qn L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
55
120...123
Min. reactive power Qn L1
REAL
var
-3.0 x 10
9
… +3.0 x 10
9
85
124...127
Fundamental voltage L1
REAL
V
0.0 ... 440.0
62122

Table of Contents