Product overview
2.3 Special considerations for use on the PROFIBUS DP and PROFINET IO
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
19
PROFIBUS DPV 0
If the DP Master does
not
support DPV1, you cannot reassign parameters which results in
the following restrictions:
There are no phase-specific parameters. All parameters apply for all three phases and
the neutral conductor.
The connection types und user data variants are limited.
The voltage transformers are not configurable (default: 1:1).
The current transformer value range primary current is restricted.
The low limit for measuring current cannot be adjusted (default: 50 mA).
Energy metering is performed continuously (the gate is not enabled).
Min/Max calculation of values is enabled (the gate is not enabled).
3P4W can be set in the parameters for the connection type 3P3W.
3P4W can be set in the parameters for the connection type 3P3W1.
Counting of operating hours is enabled (the gate is not enabled).
The residual current measurement is enabled.
Limit value monitoring cannot be used.
Energy meter default cannot be used.
The user-defined user data interface cannot be used.
The user-defined data record cannot be used.
The power quality analysis cannot be used.
The separate settings for measuring the neutral current cannot be used.
The measured value data records cannot be used.
Operation of the module on PROFINET IO
When reading data records partially from the module, please note the following:
Measured value data record DS 142:
When you read the data record with a length of 240 bytes or less, the module returns
the measured value data record DS 142 in version 2.
When you read the data record with a length of more than 240 bytes, the module
returns the measured value data record DS 142 in version 3.
Measured value data records DS 147, DS 148, DS 149:
When you read the data record with a length of 240 bytes or less, the module returns
the measured value data record in version 0.
When you read the data record with a length of more than 240 bytes, the module
returns the measured value data record in version 1.
See also
Measured value data records (Page 226)