Module versions
C.4 Module version "EE@Industry measurement data profile E0 / E1 / E2 / E3"
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
204 Manual, 07/2018, A5E42674880-AA
Table C- 8 Measurement data profile E2
Byte
Allocation
Data
type
Unit
Value range
Mea
sure
d
value
ID
0...3
Total active power L1L2L3
REAL
1 W
-3.0e+9 ... +3.0e+9
34
4...7 Total active energy L1L2L3 inflow REAL 1 Wh 0.0 ... 3.4028e+38 200
8...11
Total active energy L1L2L3 outflow
REAL
1 Wh
0.0 ... 3.4028e+38
201
Table C- 9 Measurement data profile E3
Byte
Allocation
Data
type
Unit
Value range
Mea
sure
d
value
ID
0...3 Active power L1 REAL 1 W -3.0e+9 ... +3.0e+9 13
4...7
Active power L2
REAL
1 W
-3.0e+9 ... +3.0e+9
14
8...11
Active power L3
REAL
1 W
-3.0e+9 ... +3.0e+9
15
12...15
Reactive power Qtot L1
REAL
1 var
-3.0e+9 ... +3.0e+9
22
16...19
Reactive power Qtot L2
REAL
1 var
-3.0e+9 ... +3.0e+9
23
20...23
Reactive power Qtot L3
REAL
1 var
-3.0e+9 ... +3.0e+9
24
24...31
Total active energy L1L2L3 inflow
LREAL
1 Wh
0.0 ... 1.7976e+308
210
32...39
Total active energy L1L2L3 outflow
LREAL
1 Wh
0.0 ... 1.7976e+308
211
40...47
Total reactive energy L1L2L3 inflow
LREAL
1 varh
0.0 ... 1.7976e+308
212
48...55
Total reactive energy L1L2L3 outflow
LREAL
1 varh
0.0 ... 1.7976e+308
213
56...59
Voltage UL1-N
REAL
1 V
0.0 … 1000000.0
1
60...63
Voltage UL2-N
REAL
1 V
0.0 … 1000000.0
2
64...67
Voltage UL3-N
REAL
1 V
0.0 … 1000000.0
3
68...71
Voltage UL1-UL2
REAL
1 V
0.0 … 1000000.0
4
72...75
Voltage UL2-UL3
REAL
1 V
0.0 … 1000000.0
5
76...79
Voltage UL3-UL1
REAL
1 V
0.0 … 1000000.0
6
80...83
Current L1
REAL
1 A
0.0 … 100000.0
7
84...87
Current L2
REAL
1 A
0.0 … 100000.0
8
88...91
Current L3
REAL
1 A
0.0 … 100000.0
9
92...95 Power factor L1 REAL - 0.0 … 1.0 19
96...99
Power factor L2
REAL
-
0.0 … 1.0
20
100...10
3
Power factor L3 REAL - 0.0 … 1.0 21
Structure of output user data
The structure of the 20-byte output user data is fixed and is identical to the output user data
(control bytes) of the Module version "32 I / 20 Q" (Page 195).