Measured value data records
E.2 Measured value data record for base measurements (DS 142)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
231
274...277 Fundamental apparent power L1 REAL VA -3.0 x 10
9
... +3.0 x 10
9
62125
Fundamental apparent power L2
9
9
282...285 Fundamental apparent power L3 REAL VA -3.0 x 10
9
... +3.0 x 10
9
62325
Fundamental reactive power L1
9
9
Fundamental reactive power L2
9
9
Fundamental reactive power L3
9
9
Fundamental active power L1
9
9
Fundamental active power L2
9
9
Fundamental active power L3
9
9
Fundamental cos φ active factor L1
Fundamental cos φ active factor L2
Fundamental cos φ active factor L3
Harmonic distortion (THD+N) voltage L1
Harmonic distortion (THD+N) voltage L2
Harmonic distortion (THD+N) voltage L3
Harmonic distortion (THD+N) current L1
Harmonic distortion (THD+N) current L2
Harmonic distortion (THD+N) current L3
346...358 Current module time PNI-
sec 65497
If you operate the AI Energy Meter HF with connection type 3P4W, 3P4W1 or 3P3W, the
neutral current is also calculated under the following conditions:
● Transmission factors of all phase currents (primary and secondary currents) are identical.
● Measured phase currents are greater than the value of the "Low limit for measuring
current parameter.
● The parameter "Reverse current direction" must be the same on all phases.
If one of the conditions is not met, 0 is entered as the value for the neutral current. You can
read the neutral current calculated using measured value data record 142.
Data record 142 is located on the AI Energy Meter HF. Use the RDREC instruction to read
out the data record from the module. This system function block is stored in the STEP 7
library.