Measured value data records
E.3 Structure for energy counters (DS 143)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
233
Byte
Measured variable
Data
type
Unit
Value range
Meas-
ured
value
ID
96...103
Active energy outflow (initial value) L3
LREAL
Wh
0...configured full-scale
value (10
3
...10
15
)
61221
104...111 Reactive energy inflow (initial value) L3 LREAL varh 61222
112...119
Reactive energy outflow (initial value) L3
LREAL
varh
61223
120...127 Apparent energy (initial value) L3 LREAL VAh 61224
128...129
Overflow counter active energy inflow L1
UINT
-
During reading:
0...65535
During writing for continu-
ous counting:
0
During writing for periodic
counting:
0...65500
61190
130..131
Overflow counter active energy outflow L1
UINT
-
61191
132...133
Overflow counter reactive energy inflow L1
UINT
-
61192
134...135
Overflow counter reactive energy outflow L1
UINT
-
61193
136...137
Overflow counter apparent energy L1
UINT
-
61194
138...139
Overflow counter active energy inflow L2
UINT
-
61210
140...141
Overflow counter active energy outflow L2
UINT
-
61211
142...143
Overflow counter reactive energy inflow L2
UINT
-
61212
144...145
Overflow counter reactive energy outflow L2
UINT
-
61213
146...147
Overflow counter apparent energy L2
UINT
-
61214
148...149
Overflow counter active energy inflow L3
UINT
-
61230
150...151
Overflow counter active energy outflow L3
UINT
-
61231
152...153
Overflow counter reactive energy inflow L3
UINT
-
61232
154...155
Overflow counter reactive energy outflow L3
UINT
-
61233
156...157
Overflow counter apparent energy L3
UINT
-
61234
158...161
Operating hours counter L1 (initial value)
REAL
h
During reading:
0...3.4x10
38
During writing:
0...10
9
65505
162...165 Operating hours counter L2 (initial value) REAL h 65506
166...169 Operating hours counter L3 (initial value) REAL h 65507