Reading and processing measured values
6.2 Quality information
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
48 Manual, 07/2018, A5E42674880-AA
Quality information with measured value ID 65500, 65501 or 65502 for phase-specific
measurement
The module provides quality information for phase-specific measurement in phase 1, phase
2 or phase 3 with:
User data (with measured value ID 65500, 65501 or 65502)
Measured value data record DS 147, 148 or 149
Measured value IDs 65500, 65501 and 65502 provide information on:
Current of the phase in question
Voltage of the phase in question
Operating quadrant of the phase in question
In contrast to the assignment for measured value ID 65503 (figure above), measured value
IDs 65500, 65501 and 65502 only contain the phase-specific information for current, voltage
and operating quadrant. The information about the other phases and the rotating field have
the value 0.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C