Technical specifications
8.4 Electromagnetic compatibility
SIMATIC IPC PX-39A PRO
Operating Instructions, 11/2022, A5E51699950-AA
91
8.4 Electromagnetic compatibility
See the note in "Applicability of technical specifications (Page 88)".
Interference emission
EN 61000-6-4, CAN/CSA CISPR22 class A; KS C 9832, FCC class A
Immunity to interference
EN 61000-6-1; EN 61000-6-2; KS C 9835
Interference immunity on the sup-
ply cables
± 2 kV according to IEC 61000-4-4; burst
± 1 kV according to IEC 61000-4-5; symmetrical surge
± 2 kV according to IEC 61000-4-5; asymmetrical surge
Noise immunity on signal lines
± 1 kV acc. to IEC 61000-4-4; Burst; Length < 30 m
± 2 kV acc. to IEC 61000-4-4; Burst; Length > 30 m
± 2 kV acc. to IEC 61000-4-5; Surge; Length > 30 m
Immunity to electrostatic dis-
charge
± 6 kV contact discharge in accordance with IEC 61000-4-2
± 8 kV air discharge in accordance with IEC 61000-4-2
Immunity to RF interference
10 V/m 80 MHz 2.7 GHz,
80% AM to IEC 61000-4-3
3 V/m 2.7 – 6 GHz,
80% AM to IEC 61000-4-3
10 V 10 KHz 80 MHz,
80% AM to IEC 61000-4-6
Immunity to magnetic fields
100 A/m; 50 Hz; 60 Hz (according to IEC 61000-4-8)
8.5 Ambient conditions
See the note in "Applicability of technical specifications (Page 88)".
Climatic ambient conditions (standard operating position / inclined mounting)
Maximum permitted ambient temperature during operation
Temperature, tested according to IEC 60068-2-1, IEC 60068-2-2
BIOS setting
1
High Temperature /
Stable performance
Balanced
Max. performance
Intel Celeron
6600HLE
+45 °C
2
/ +45 °C
3
+40 °C
2
/ +40 °C
3
+35 °C
2
/ +35 °C
3
Intel XEON
W-11155MLE
+45 °C
2
/ +45 °C
3
+40 °C
2
/ +40 °C
3
+35 °C
2
/ +35 °C
3
Intel XEON
W-11555MLE
+45 °C
2
/ +45 °C
3
+40 °C
2
/ +40 °C
3
+35 °C
2
/ +35 °C
3
Intel XEON
W-11865MLE
+45 °C
2
/ +45 °C
3
+40 °C
2
/ +40 °C
3
+35 °C
2
/ +35 °C
3
Relative humidity
Tested according to IEC 60068-2-78, IEC 60068-2-30
Operation
0 to 31 °C: 5 to 80%; decreasing linearly to 5 to 25% at 45 °C
Storage/transport
5 to 95% at 25/55 °C, no condensation