8 outputs in one group
The output can be configured for each channel:
Possible selection As of product version Ranges
Current output Product version 1
0 mA to 20 mA
4 mA to 20 mA
+/-20 mA
Voltage output Product version 3
1 V to 5 V
0 V to 10 V
+/-10 V
Resolution 12 bits
HART-compliant (for current output)
Configurable diagnostics
Configurable diagnostic interrupt
Floating relative to backplane bus interface and load voltage
Configuration in Run (CiR) supported
Note
When the rated load voltage (L+) is switched off and on, the outputs can output incorrect
voltage/current values for approximately 500 ms.
ET 200PA SMART I/O modules
10.5 Analog output modules
ET 200PA SMART
202 Operating Instructions, 06/2019, A5E34192013-AB