Commissioning
12.3 Commissioning procedure
S7-1500R/H redundant system
370 System Manual, 01/2024, A5E41814787-AF
Automatic assignment
Requirement:
Both real CPUs of the redundant system have the same redundancy ID (e.g."1").
Options for automatic assignment:
Both CPUs are in STOP. There is pairing between the two CPUs. The ERROR LEDs are
flashing red.
Procedure: Switch the left-hand CPU in the configuration to the RUN operating state.
Result: The right-hand CPU in the configuration changes its redundancy ID.
The left-hand CPU in the configuration is in RUN operating state. The right-hand CPU in
the configuration is in STOP. Both redundancy connections are separated, therefore there
is no pairing between the two CPUs.
Procedure: Implement pairing between the two CPUs by establishing at least one
redundancy connection. Result: The right-hand CPU in the configuration changes its
redundancy ID.
The left-hand CPU in the configuration is in RUN. The right-hand CPU in the configuration
is in POWER OFF. At least one redundancy connection is established. There is no pairing
between the two CPUs due to POWER OFF.
Procedure: POWER ON the right-hand CPU in the configuration. Result: The right-hand
CPU in the configuration changes its redundancy ID.
Assignment using the display
Requirements:
The two real CPUs in the redundant system:
Are connected to each other
Have redundancy ID 1
The mode selector switches of the CPUs are in the STOP position
Both CPUs are in POWER OFF mode
Procedure:
Proceed as follows to assign the redundancy IDs via the CPU display:
1. POWER ON the CPU to which you want to assign redundancy ID 2.
2. On the display of that CPU, select the menu command "Overview > Redundancy". Assign the
CPU redundancy ID 2.
Once you have assigned the CPU redundancy ID 2, the CPU will automatically restart.
3. Switch the other CPU POWER OFF.

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals