Number of inputs 16
Cable length
Unshielded, input delay
0.5 ms
3 ms
10 / 20 ms
Maximum 100 m
Maximum 600 m
Maximum 600 m
Cable length, shielded
1000 m
Voltage, current and potential
Number of inputs that can be enabled simultaneously 16
Electrical isolation
Between channels and backplane bus
Yes
Between channels
in groups of
Yes
1
Permissible potential difference
Between different circuits
60 V DC/30 V AC (SELV)
Insulation tested at
Channels to backplane bus and load voltage L+
1500 V AC
Between channels
1500 V AC
Current consumption
from backplane bus (5 V)
Maximum 150 mA
Module power loss Typ. 8 W
Status, interrupts, diagnostics
Status display Green LED per channel
Interrupts
Hardware interrupt
Configurable
Diagnostic interrupt
Configurable
Diagnostic functions Configurable
Group fault display
for internal fault
for external fault
red LED (INTF)
red LED (EXTF)
Channel fault display
None
Diagnostic information can be read out
Possible
Monitoring for
Wire break
I > 0.7 mA
Substitute values can be connected No
Data for selecting a sensor
Input voltage
Rated value
UC 24 to 60 V
For "1" signal
15 to 72 V DC
- 15 to -72 V DC
15 to 60 V AC
For "0" signal
DC - 6 to +6 V
AC 0 to 5 V
Frequency range DC/AC 47 to 63 Hz
Digital modules
4.10 Digital input module SM 421; DI 16 x UC 24/60 V (6ES7421-7DH00-0AB0)
S7-400 Automation System Module Data
114 Reference Manual, Ausgabe 11/2016, A5E00850736-08