EasyManua.ls Logo

Siemens Simatic S7-400 - Page 115

Siemens Simatic S7-400
472 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input current
For "1" signal
Typ. 4 to 10 mA
Input characteristic as IEC 61131-2
1)
Connection of 2-wire BEROs
Permissible quiescent current
Possible
Maximum 0.5 to 2 mA
2)
Time, frequency
Internal processing time for
hardware interrupt enable only
Maximum 450 µs
Hardware and diagnostic interrupt enable
Maximum 2 ms
Input delay
Configurable
Yes
Rated value
0.5 / 3 / 10 / 20 ms
Values included in cycle and response times.
Sensor circuit
Sensor resistor circuit for wire-break monitoring
Rated voltage 24 V(15 to 35 V)
18 kΩ
Rated voltage 48 V(30 to 60 V)
39 kΩ
Rated voltage 60 V(50 to 72 V)
56 kΩ
1
IEC 61131-2 does not specify any data for UC modules. The values were, however, adjusted as far
as possible to IEC 61131-2.
2
Minimum quiescent current is required for wire break monitoring.
Digital modules
4.10 Digital input module SM 421; DI 16 x UC 24/60 V (6ES7421-7DH00-0AB0)
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08 115