shielded
1000 m
Voltage, current and potential
Rated supply voltage of electronics L+ None
Number of inputs that can be enabled simultaneously 16
Electrical isolation
Between channels and backplane bus
Yes
Between channels
in groups of
Yes
4
Permissible potential difference
Between M
intern
and the inputs
250 V AC (reinforced insulation)
Test voltage:
4000 Vac (type test)
2400 AC (routine test)
Between inputs of different groups
500 V AC (basic insulation)
Test voltage:
2400 Vac (routine test)
2300 Vac (type test)
Current consumption
From backplane bus (5 V)
Maximum 80 mA
Module power loss Typ. 12 W
Status, interrupts, diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic functions None
Substitute values can be connected No
Data for selecting a sensor
Input voltage
Rated value
UC 120/230 V
For "1" signal
74 to 264 V AC
80 to 264 V DC
-80 to -264 V DC
For "0" signal
0 to 40 V AC
-40 to +40 V DC
Frequency range 47 to 63 Hz
Input current
For "1" signal (120 V)
Typ. 10 mA AC
Typ. 1.8 mA DC
For "1" signal (230 V)
Typ. 14 mA AC
Typ. 2 mA DC
For "0" signal
0 to 6 mA AC
0 to 2 mA DC
Input delay
For "0" to "1"
Maximum 20 ms AC
Maximum 15 ms DC
Digital modules
4.12 Digital input module SM 421; DI 16 x UC 120/230 V (6ES7421-1FH20-0AA0)
S7-400 Automation System Module Data
124 Reference Manual, Ausgabe 11/2016, A5E00850736-08