Technical specifications of the SM 432; AO 8 x 13 bit
Dimensions and weight
Dimensions W x H x D (mm) 25 x 290 x 210
Weight ca. 650 g
Module-specific data
Number of outputs 8
Cable length
Shielded
Maximum 200 m
Voltage, current and potential
Supply voltage of electronics L+ 24 V DC
Rated load voltage L+ 24 V DC
Reverse polarity protection
Yes
Electrical isolation
Between channels and backplane bus
Yes
Between channels
No
Between channels and load voltage L+
Yes
Permissible potential difference
between the outputs (UCM)
3 V DC
between S- and MANA (UCM)
3 V DC
Between MANA and Mintern (UISO)
60 V DC/30 V AC (SELV)
Insulation tested at
Between bus and L+/M
2120 V DC
Between bus and analog section
2120 V DC
Between bus and chassis ground
500 V DC
Between analog section and L+/M
500 V DC
Between analog section and chassis ground
2120 V DC
Between L+/M and chassis ground
2120 V DC
Current consumption
From backplane bus (5 V)
Maximum 150 mA
Supply and load voltage L+ (at rated load)
Maximum 400 mA
Supply and load voltage L + (no load)
Maximum 200 mA
Module power loss typ. 9 W
Formation of analog values
Resolution (including overrange) 13 bits
Conversion time (per channel)
in the ranges 1 to 5 V and 4 to 20 mA
420 µs
in all ranges
300 µs
Basic execution time of the module (all channels enabled)
in the ranges 1 to 5 V and 4 to 20 mA
3.36 ms
in all other ranges
2.4 ms
Settling time
for resistive load
0.1 ms
Analog modules
5.26 Analog output module SM 432; AO 8 x 13 Bit (6ES7432-1HF00-0AB0)
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08 319