9.3 Modbus RTU library
S7-200 SMART
482 System Manual, V2.3, 07/2017, A5E03822230-AF
Parameter
Parity
is set to match the parity of the Modbus slave device. All settings use one
start bit and one stop bit. The allowed values are: 0 (no parity). 1 (odd parity), and 2 (even
parity).
Parameter
Port
sets the physical communication port (0 = RS-485 integrated in CPU, 1 =
RS-485 or RS-232 located on the optional CM01 signal board).
Parameter
Timeout
is set to the number of milliseconds to wait for the response from the
slave. The Timeout value can be set anywhere in the range of 1 millisecond to 32767
milliseconds. A typical value would be 1000 milliseconds (1 second). The Timeout parameter
should be set to a value large enough so that the slave device has time to respond at the
selected baud rate.
The Timeout parameter is used to determine if the Modbus slave device is responding to a
request. The Timeout value determines how long the Modbus Master will wait for the first
character of the response after the last character of the request has been sent. The Modbus
master will receive the entire response from the Modbus slave device if at least one
character of the response is received within the Timeout time.
When the MBUS_CTRL / MB_CTRL2 instruction completes, the instruction returns TRUE for
the Done output.
The Error output contains the result of executing the instruction.
See also
Modbus RTU master execution error codes (Page 487)