9.4 Open user communication library
S7-200 SMART
506 System Manual, V2.3, 07/2017, A5E03822230-AF
Note that the S7-200 SMART does not automatically attempt to reconnect to a device after
the connection has been closed. If the remote device breaks the device connection, your
program must execute another ISO_CONNECT instruction to reconnect the device. This is
true for both active and passive connections.
Table 9- 15 Parameters of the ISO_CONNECT instruction
Parameter
Declaration
Data type
Description
EN
IN
BOOL
Enable input
Req IN BOOL The CPU starts the connect operation if Req =
TRUE. If Req = FALSE, then the outputs show
the current status of the connection.
Active IN BOOL
TRUE = active connection
FALSE = passive connection
ConnID IN WORD The CPU uses the Connection ID (ConnID) num-
ber to identify this connection for the other in-
structions. The possible ConnID range is 0 to
65534.
IPaddr1
...
IPaddr4
IN BYTE These are the four IP address octets. IPaddr1 is
the most significant byte and IPaddr4 is the least
significant byte of the IP address.
RemTsap IN DWORD The RemPort is the remote TSAP string. The
program uses a pointer to pass the string. (Refer
to the example following this table for more in-
formation.)
LocTsap IN DWORD The LocPort is the local TSAP string. The pro-
gram uses a pointer to pass the string. (Refer to
the example following this table for more infor-
mation.)
Done OUT BOOL The instruction sets the Done output when the
connect operation is complete with no errors.
Busy OUT BOOL The instruction sets the Busy output while the
connection operation is in progress.
Error OUT BOOL The instruction sets the Error output when the
connection operation is complete with an error.
Refer to "Open user communication library in-
struction error codes" (Page 524) for further in-
formation.
Status OUT BYTE The Status output shows the error code if the
instruction sets the Error output. Status is zero
(no error) if the instruction sets the Busy or Done
outputs.