Open loop motion control 
  12.10 Advanced topics 
S7-200 SMART 
System Manual, V2.3, 07/2017, A5E03822230-AF 
665 
Table 12- 39  Configuration/Profile table: Interactive block 
Configuration/Profile table 
78  MOVE_CMD  Selects the mode of operation (1 byte): 
•  0: Absolute position 
•  1: Relative position 
•  2: Single-speed, continuous positive rotation 
•  3: Single-speed, continuous negative rotation 
•  4: Manual speed control, positive rotation 
•  5: Manual speed control, negative rotation 
•  6: Single-speed, continuous positive rotation with 
triggered stop (Activation of RPS triggers the stop; 
TARGET_POS contains distance to travel after 
signal) 
•  7: Single-speed, continuous negative rotation with 
triggered stop (Activation of RPS triggers the stop; 
TARGET_POS contains distance to travel after 
signal) 
•  8 to 255: Reserved (error if specified) 
-- 
Target position to go to in this move (4 bytes) 
84  TGT_SPEED  Target speed for this move (4 bytes)  DInt/Real 
Absolute position of the reference point (4 bytes)