Technical specifications
A.3 Digital inputs and outputs expansion modules (EMs)
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
729
EM Digital
8 x Outputs
(EM DT08)
EM Digital
8 x Outputs Relay
(EM DR08)
EM Digital
16 x Outputs Relay
(EM QR16)
EM Digital
16 x Outputs Transis-
tor (EM QT16)
Output behavior in STOP Last value or substi-
tute value (default
Last value or substi-
tute value (default
Last value or substi-
tute value (default
Last value or substi-
tute value (default
Number of outputs on simulta-
neously
8 8
• 8 (no adjacent
points) at 60 °C
horizontal or 50
°C vertical
• 16 at 55 °C
horizontal or 45
°C vertical
16
Cable length (max.), in meters Shielded: 500 m
Shielded: 500 m
Shielded: 500 m
Unshielded: 150 m
Shielded: 500 m
Unshielded: 150 m
Table A- 76 Wiring diagrams for the EM DT08 Digital 8 x Outputs (6ES7288-2DT08-0AA0) and EM
DR08 Digital 8 x Outputs x Relay (6ES7288-2DR08-0AA0)
EM DT08 Digital 8 x Outputs
(6ES7288-2DT08-0AA0)
EM DR08 Digital 8 x Outputs x Relay
(6ES7288-2DR08-0AA0)