Technical specifications
A.3 Digital inputs and outputs expansion modules (EMs)
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
733
Table A- 83 Digital inputs
EM Digital
8 x Inputs/
Digital 8 x Outputs
(EM DT16)
EM Digital
8 x Inputs/
8 x Relay Outputs
(EM DR16)
EM Digital
16 x Inputs/ Digital
16 x Outputs
(EM DT32)
EM Digital
16 x Inputs /
16 x Relay Outputs
(EM DR32)
Type Sink/Source (IEC
Type 1 sink)
Sink/Source (IEC
Type 1 sink)
Sink/Source (IEC
Type 1 sink)
Sink/Source (IEC
Type 1 sink)
Rated voltage 24 V DC at 4 mA,
24 V DC at 4 mA,
24 V DC at 4 mA,
24 V DC at 4 mA,
Continuous permissible voltage
Surge voltage 35 V DC for 0.5
35 V DC for 0.5
35 V DC for 0.5
35 V DC for 0.5 sec.
Isolation (field side to logic) 500 V AC for 1
500 V AC for 1
500 V AC for 1
500 V AC for 1 mi-
Filter times 0.2, 0.4, 0.8, 1.6,
3.2, 6.4, and 12.8
ms, selectable in
0.2, 0.4, 0.8, 1.6,
3.2, 6.4, and 12.8
ms, selectable in
0.2, 0.4, 0.8, 1.6,
3.2, 6.4, and 12.8
ms, selectable in
0.2, 0.4, 0.8, 1.6, 3.2,
6.4, and 12.8 ms,
selectable in groups
Number of inputs on simultane-
8 8 16 16
Cable length (max.), in meters Shielded:
500 m normal in-
puts
Unshielded:
300 m normal in-
Shielded:
500 m normal in-
puts
Unshielded:
300 m normal in-
Shielded:
500 m normal in-
puts
Unshielded:
300 m normal in-
Shielded:
500 m normal inputs
Unshielded:
300 m normal inputs