Configuration
3.19 Telecontrol connections
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
101
●
Max. number of statistics queries
If the configured number of statistics requests of the master is exceeded within the key
exchange interval, the module enters a message in the diagnostics buffer of the CPU.
Range of values: 2...255 Default setting: 5
●
Authentication requests before key exchange
Maximum number of authentication requests of the module to the master. When this
number is reached, the session key is renewed.
Range of values: 1...10000 Default setting: 1000
Recommendation: Set the number for the station module twice as high as for the master.
●
Period after which the key is exchanged again between the station module and the
master. The interval must be matched up on both communications partners.
Range of values: 0...65535 min. at 0 (zero), the key is never changed (function disabled).
Default setting: 15 min.
Recommendation: Set the key exchange interval for the station module twice as high as
for the master.
●
Maximum wait time of the module after an authentication request to the master. If the
waiting time for the response from the master is exceeded, the module generates a
security event and sends this to the master.
Range of values: 1... 65535 s Default setting: 5
●
The pre-shared key can be configured in two ways:
– Manual configuration
Enter the pre-shared key in STEP 7 manually as a hexadecimal value.
– Import as file
Import the pre-shared key from the file system of the engineering station if the pre-
shared key was generated by the master or another system.
The pre-shared key of a station module must be identical to the pre-shared key of the
master.