Communication mechanisms
2.2 Communications options
Configuration - DNP3
26 Configuration Manual, 11/2018, C79000-G8976-C508-01
DNS server address(es)
You require the DNS server address if you address the master using a name that can be
resolved by DNS.
Partner number
Stations that communicate with the master require the partner number of the master in
order to assign the data points to be transferred.
With S7-1200 CPs that can only function as stations, the partner number of the master is
assigned by the system.
Redundant masters
The two devices of a redundant master have an identical station address.
They only require different IP addresses or host names.
Configurations with connections over the Internet: VPN connections
For connections running via the Internet, dynamic IP addresses can be used.
To allow communication in both directions and to ensure that the data is protected during
transfer, a connection with a VPN tunnel is necessary. For this the security modules of the
SCALANCE S or SCALANCE M series are available.
Remember the following points when configuring:
You configure the IP address of the master station on the master.
When configuring the interface of the station module, you configure the IP address of the
router.
You perform the VPN configuration with SCALANCE S/M both for the station and for the
master station in STEP 7.
2.2
Communications options
Communication paths
The following communication channels are possible:
Connections between master and station
Redundant connections
If two subscribers can be reached via different networks, you can create a maximum of
two connections between the subscribers to establish path redundancy.